Fire codes and standards require that fire dampers are tested, maintained, and inspected with documentation at regular intervals, after installation, and throughout their intended life, to ensure that they operate correctly and as intended when needed.
The codes/standards that note these requirements are:
- NFPA 80 – Fire Doors and Other Opening Protectives
- NFPA 90A – Installation of Air-Conditioning and Ventilating Systems
- BS 9999 – Code of Practice for Fire Safety in the Design, management, and use of Buildings
The below article will concentrate on the drop-type, actuated, and monitored type mechanical fire damper, and how they should be inspected and tested from completion of installation till the end of their working life.
If you want to read more about fire dampers, please see our article FIRE DAMPERS | Ultimate Understanding and Selection
How often should fire dampers be tested/maintained and inspected?
Fire dampers should be tested under 3 activities, with the code requirements listed below:
- 1. Operational Test
- 2. Acceptance Test
- 3. Periodic Test
Operational Testing | Acceptance Testing | Periodic Inspection | |
NFPA 80 [Chapter 19] | Directly after installation | Directly after installation | 1 year after Operational/Acceptance Testing then every 4 years or 6 years if a hospital |
NFPA 90A [Chapter 7] | n/a | Prior to the occupation of the building | n/a |
BS 9999 [Annex W]* | n/a | Directly after installation | each 1 year after Operational/Acceptance Test |
*Within BS9999 its notes that dampers installed in dirty/dusty environments should be tested more regularly in line with the pollution encountered. This should be detailed by the facility managers.
Who can test the fire dampers?
NFPA 80 [Section 19.4.1] – notes that fire damper inspection and testing should be completed by a person who is qualified with knowledge and who understands the operation and design of the systems being worked upon.
What Fire damper testing tools can we use?
The usual tools that are used to drop test and reset dampers are our hands, however, this has its risks, and sometimes it’s just hard work.
There are many testing tools that can help on the market, just do a google search and they will all come up.
How are fire dampers tested and inspected?
Although dampers are extremely critical in protecting people and buildings during an emergency the inspection and testing requirements are quite basic as noted in the codes and standards, but very important.
The fire damper inspection checklists/works, and testing should consist of the following sequence:
- Pre-inspection works
- Review of documentation and certificates
- Visual inspection
- Operational, acceptance, and periodic testing
each should include a fire damper inspection checklist
Inspections, checks, and testing for a fire damper that USES a FUSIBLE LINK
Pre-Inspection works
Prior to visually inspecting and testing the fire dampers, we should understand the building and its systems by completing a comprehensive desktop study.
TEMPERATURE = 165F (74C) / STANDARDS = UL Standard 33 (Underwriters Laboratory Listed)
FITS: Laundry & Trash Chute Discharge Doors / DAMPERS: Dayton. Lloyd Industries, Ruskin and other manufacturers
Below are some pointers that should be considered:
Ref | Review |
1.0 | Obtain all drawings [layout and schematics] of the systems that will be inspected and tested |
2.0 | If there are no drawings or the information provided is confusing then a full onsite review should be conducted, starting with the locations of the fire barriers etc. |
3.0 | Review the overall layout of the building making note of locations of equipment and systems etc |
4.0 | Review the damper locations and quantities that will be inspected and tested |
5.0 | Understand if there are any systems, which the dampers are installed, would be considered hazardous and need specialized personal protective equipment [PPE], tools, or resources |
6.0 | Review the dampers and their design intent, are they static dampers or dynamic dampers |
7.0 | If the damper is designed to be static – can the fans be shut down to allow testing, not affecting other areas. |
8.0 | If the damper is designed to be dynamic – the fans may be switched off under NFPA 19.5.2.2.2 to test, or if site restrictions don’t allow this – check what areas of the building/systems will be impacted. |
9.0 | Understand the permits that will be required to conduct the works |
10.0 | Will works need to be conducted out of hours |
11.0 | Based upon the number of dampers, what is the expected time period to complete the works. |
Fusible fire damper testing documents and certification
NPFA-80 [Chapter 19], requires all documentation related to proving the inspection and testing of the dampers should include the following information [as noted with ‘Yes’ bold], we have added some other information that would be useful:
Ref | Description | Required |
1.0 | Location of Damper | Yes |
2.0 | Damper Number | Optional |
3.0 | Ventilation System | Optional |
4.0 | Static Designed Damper | Optional |
5.0 | Dynamic Designed Damper | Optional |
6.0 | Date of Inspection | Yes |
7.0 | Inspector Name | Yes |
8.0 | Inspector Company | Optional |
9.0 | Observations/Deficiencies [space for] | Yes |
10.0 | Observations/Deficiencies Close Out [space for] | Yes |
All documentation should be kept and maintained for at least three test cycles and made available for review by the AHJ.
Often there are issues with gaining access to certain spaces, whether that be an installation issue or someone has come later and blocked the access.
If that is the case we would use this type of Borescope Inspection Camera to get into and see everything.
Visual Inspection
Prior to the damper testing taking place, we should conduct a visual inspection to ensure that there is access, it is installed and there are no obvious problems that can be seen.
Ref | Check | Notes |
1.0 | Permit applied for and granted to conduct works based upon the Pre-Inspection findings above. | |
2.0 | PPE available. | Hard hat, glasses/goggles, long sleeve shirt, arm protector, hi-vis, gloves, boots. |
3.0 | Access available. | Working platform |
4.0 | The operative conducting the inspecting and testing of the fire dampers is qualified to do so. | |
5.0 | All documentation and records for inspection and testing are in line with NFPA Chapter 19 requirements. | |
6.0 | Manufacturers’ installation & maintenance instructions are available, attached, and have been reviewed. | |
7.0 | The damper is labeled in line with NFPA 90A [Section 4.3.5.2]. | Access to dampers shall be identified with letters having a minimum height of 12.7 mm (1⁄2 in.) to indicate the location of the fire protection device(s) within. |
8.0 | Access in line with NFPA 90A [Section 7.2.1] | An access door shall be provided that is not less than 12 in. (305 mm) square or provided with a removable duct section |
9.0 | Type of access provided | Note if an access door or Removable Section |
10.0 | Access is clear and not obstructed | |
11.0 | Breakaway connection installed | In line with manufacturers’ requirements |
12.0 | Installation of fire damper in line with manufacturers’ instructions | Sleeves, mounting, types of fasteners etc. |
13.0 | Confirm Fire Dampers are UL555 rated | |
14.0 | Visually confirm that the damper is in the fully open position or fully closed as required by the design | Note if open or if closed is that the design?. |
15.0 | Visually confirm there are no obstructions or foreign objects that will affect the operation of the damper | |
16.0 | Check that the damper is not painted | |
17.0 | Visually confirm that the damper is clean and free of dust/dirt | If it is not, then clean and confirm the damper has been cleaned |
Operational, acceptance, and periodic testing of fire damper USING a fusible link
Once the visual inspection has been concluded the following testing should commence, with any observations being logged and noted in the observations field of the testing document.
If during the inspecting and/or testing a non-compliant damper is noted, then remedial works should be completed immediately and all visual inspections and physical testing repeated and documented.
Ref | Activity | Notes |
1.0 | Check the status of system fans [airflow] and ensure are switched off or still running based upon permit | |
2.0 | Remove access panel/section of ducting to gain access | |
3.0 | Remove/activate the fusible link to drop the damper | |
4.0 | Ensure damper drops cleanly with no intervention needed and fully 100% | |
5.0 | If the damper has a latch holding the damper fully closed, ensure the latch operates | |
6.0 | Inspect fusible link for wear, defects and to make sure not painted | Note if the link was replaced or not. If the link is replaced then it should be UL approved and in line with the manufacturer’s literature. |
7.0 | Reset the damper to the fully open position | |
8.0 | Reinstate or replace the fusible link | |
9.0 | Ensure that the damper is unobstructed and fully operational before completing | |
10.0 | Complete all documentation and log and file |
Inspections, checks, and testing for an Actuated Fire Damper not using a Fusible Link
The below works are related to dampers that would use an electronic or pneumatic actuator to control their opening, usually closing via a spring.
Note that in line with NFPA, Fans are not permitted to be shut down during this type of test.
Pre-Inspection works
As with the previous sections, prior to visually inspecting and testing the dampers, we need to understand the building and its systems by completing a comprehensive desktop study, some pointers below:
Ref | Review |
1.0 | Obtain all drawings [layout and schematics] of the systems that will be inspected and tested |
2.0 | If there are no drawings or the information provided is confusing then a full onsite review should be conducted, starting with the locations of the fire barriers etc. |
3.0 | Review the overall layout of the building making note of locations of equipment and systems etc |
4.0 | Review the damper locations and quantities that will be inspected and tested |
5.0 | Understand if there are any systems, which the dampers are installed, would be considered hazardous and need specialized personal protective equipment [PPE], tools, or resources |
6.0 | Ensure that during the testing the fans are able to operate [in line with NFPA 19.5.2.3.1] |
7.0 | Check what areas of the building/systems will be impacted by the testing. |
8.0 | Understand the permits that will be required to conduct the works |
9.0 | Will works need to be conducted out of hours |
10.0 | Based upon the number of dampers, what is the expected time period to complete the works. |
Actuated Fire damper testing documents and certification
As with the fusible link requirements above, NPFA-80 [Chapter 19], requires all documentation related to proving the inspection and testing of the dampers should include the following information [as noted with ‘Yes’ bold], we have added some other information that would be useful.
Ref | Description | Required |
1.0 | Location of Damper | Yes |
2.0 | Damper Number | Optional |
3.0 | Ventilation System | Optional |
4.0 | Static Designed Damper | Optional |
5.0 | Dynamic Designed Damper | Optional |
6.0 | Actuator Type [pneumatic/electronic] | Optional |
7.0 | Date of Inspection | Yes |
8.0 | Inspector Name | Yes |
9.0 | Inspector Company | Optional |
10.0 | Observations/Deficiencies [space for] | Yes |
11.0 | Observations/Deficiencies Close Out [space for] | Yes |
All documentation should be kept and maintained for at least three test cycles and made available for review by the AHJ.
Visual Inspection
Prior to the damper testing taking place, we should conduct a visual inspection to ensure that there is access, it is installed and there are no obvious problems that can be seen.
Ref | Check | Notes |
1.0 | Permit applied for and granted to conduct works based upon the Pre-Inspection findings above. | |
2.0 | PPE available. | Hard hat, glasses/goggles, long sleeve shirt, arm protector, hi-vis, gloves, boots. |
3.0 | Access available. | Working platform |
4.0 | The operative conducting the inspecting and testing of the fire dampers is qualified to do so. | |
5.0 | All documentation and records for inspection and testing in line with NFPA Chapter 19 requirements. | |
6.0 | Manufacturers’ installation & maintenance instructions are available, attached, and have been reviewed. | |
7.0 | The damper is labeled in line with NFPA 90A [Section 4.3.5.2]. | Access to dampers shall be identified with letters having a minimum height of 12.7 mm (1⁄2 in.) to indicate the location of the fire protection device(s) within. |
8.0 | Access in line with NFPA 90A [Section 7.2.1] | An access door shall be provided that is not less than 12 in. (305 mm) square or provided with a removable duct section |
9.0 | Type of access provided | Note if an access door or Removable Section |
10.0 | Access is clear and not obstructed | |
11.0 | Breakaway connection installed | In line with manufacturers’ requirements |
12.0 | Installation of fire damper in line with manufacturers’ instructions | Sleeves, mounting, types of fasteners etc. |
13.0 | Ensure the actuator is the one that was attached to the damper when purchased and is still installed as per UL and the manufacturer’s requirements. | The requirements are the damper actuator should not be replaced and should be attached to the damper at the factory. |
14.0 | Confirm Fire Dampers are UL555 rated | |
15.0 | Visually confirm that the damper is in the fully open position or fully closed as required by the design | Note if open or if closed is that the design?. |
16.0 | Visually confirm there are no obstructions or foreign objects that will affect the operation of the damper | |
17.0 | Check that the damper is not painted | |
18.0 | Visually confirm that the damper is clean and free of dust/dirt | If it is not, then clean and confirm the damper has been cleaned |
19.0 | Visually inspect and confirm that the actuator is unobstructed, undamaged, and clean |
Operational, acceptance, and periodic testing of actuated fire damper not using a fusible link
Once the visual inspection has been concluded the following testing should commence, with any observations being logged and noted in the observations field of the testing document.
If during the inspecting and/or testing a non-compliant damper is noted, then remedial works should be completed immediately and all visual inspections and physical testing repeated and documented.
Ref | Activity | Notes |
1.0 | Check the status of system fans [airflow] and ensure are still running based upon permit | |
2.0 | Remove access panel/section of ducting to gain access. | |
3.0 | Command the damper to close or open via the actuator and visually confirm it closes 100% | |
4.0 | Command the damper to restore original/design position [close or open] via the actuator and visually confirm it operates to 100% | |
5.0 | Ensure that the damper is unobstructed and fully operational before completing | |
6.0 | Complete all documentation and log and file |
Inspections, checks, and testing of Actuated fire damper not using a fusible link that has a Remote Inspection
The below works are related to dampers that would be remotely monitored using an electronic or pneumatic actuator to control their opening.
Note that in line with NFPA, Fans are not permitted to be shut down during this type of test.
Refer to the below in the previous section to complete the following:
- Pre-inspection works
- Review of documentation and certificates
- Visual inspection
Operational, acceptance and periodic testing of Actuated fire damper not using a fusible link that has a Remote Inspection
Once the visual inspection has been concluded the following testing should commence, with any observations being logged and noted in the observations field of the testing document.
If during the inspecting and/or testing a non-compliant damper is noted, then remedial works should be completed immediately and all visual inspections and physical testing repeated and documented.
Ref | Activity | Notes |
1.0 | Check the status of system fans [airflow] and ensure are still running based upon permit | |
2.0 | Remove access panel/section of ducting to gain access. | |
3.0 | Visually confirm that the open/closed position indication lamps at the panel match the status of the damper | |
4.0 | Command the damper to close or open visually confirm it closes 100% and that the indication panel and lights are inline | |
5.0 | Command the damper to restore original/design position [close or open] and visually confirm it operates to 100% | |
6.0 | Ensure that the damper is unobstructed and fully operational before completing | |
7.0 | Complete all documentation and log and file |